All new customers are required to get a safety check.
Regardless of its size, any ASME container filled on site must be located so that the filling connection and fixed maximum liquid level gauge are at least 10 ft from any external source of ignition {e.g. open flame, window, A/C, compressor}, intake to direct-vented gas appliance, or intake to a mechanical ventilation system.
This distance may be reduced to no less than 10 ft. for a single container of 1200 gal. water capacity or less, provided such container is at least 25 ft. from any other LP-Gas container of more than 125 gal. water capacity.